Approach to eliminate DC-link voltage pulsations of voltage-source PWM rectifier
Published:2012-12-07 author:CHEN Jian-sheng, ZHANG Wei, XV Hai-liang Browse: 3086 Check PDF documents

Approach to eliminate DC-link voltage pulsations of voltage-source PWM rectifier

CHEN Jian-sheng, ZHANG Wei, XV Hai-liang
(College of Electrical Engineering, Zheijiang University, Hangzhou 310027, China)

Abstract: The stability of the DC-link voltage is a main target of the grid-connected PWM rectifier. When the grid voltage is unbalanced and (or)harmonically distorted,the conventional control strategy can’t eliminate the pulsation of DC-link voltage. In order to solve this problem,Firstly,the effect of unbalanced and 5th and 7th harmonics to the VSR was analyzed;and then,an approach based on PI-R controller was proposed,with detail calculation of the current references and designation of current controller. Simulation results of a 1 MW VSR indicate that the proposed control strategy can significantly reduce the DC-link voltage pulsation,enhance the operation of the DC-link capacitor and the associated load safely.
Key words: voltage-source PWM rectifier(VSR); harmonic distortion; proportional integral plus resonant(PI-R) controller; DC-link voltage
 