International Standard Serial Number:

ISSN 1001-4551

Sponsor:

Zhejiang University;

Zhejiang Machinery and Electrical Group

Edited by:

Editorial of Journal of Mechanical & Electrical Engineering

Chief Editor:

ZHAO Qun

Vice Chief Editor:

TANG ren-zhong,

LUO Xiang-yang

Tel:

86-571-87041360,87239525

Fax:

86-571-87239571

Add:

No.9 Gaoguannong,Daxue Road,Hangzhou,China

P.C:

310009

E-mail:

meem_contribute@163.com

Approach to eliminate DC-link voltage pulsations of voltage-source PWM rectifier
Published:2012-12-07 author:CHEN Jian-sheng, ZHANG Wei, XV Hai-liang Browse: 3620 Check PDF documents

Approach to eliminate DC-link voltage pulsations of voltage-source PWM rectifier

CHEN Jian-sheng, ZHANG Wei, XV Hai-liang
(College of Electrical Engineering, Zheijiang University, Hangzhou 310027, China)

Abstract: The stability of the DC-link voltage is a main target of the grid-connected PWM rectifier. When the grid voltage is unbalanced and (or)harmonically distorted,the conventional control strategy can’t eliminate the pulsation of DC-link voltage. In order to solve this problem,Firstly,the effect of unbalanced and 5th and 7th harmonics to the VSR was analyzed;and then,an approach based on PI-R controller was proposed,with detail calculation of the current references and designation of current controller. Simulation results of a 1 MW VSR indicate that the proposed control strategy can significantly reduce the DC-link voltage pulsation,enhance the operation of the DC-link capacitor and the associated load safely.
Key words: voltage-source PWM rectifier(VSR); harmonic distortion; proportional integral plus resonant(PI-R) controller; DC-link voltage
 

  • Chinese Core Periodicals
  • Chinese Sci-tech Core Periodicals
  • SA, INSPEC Indexed
  • CSA: T Indexed
  • UPD:Indexed


2010 Zhejiang Information Institute of Mechinery Industry

Technical Support:Hangzhou Bory science and technology

You are 1895221 visit this site