International Standard Serial Number:

ISSN 1001-4551

Sponsor:

Zhejiang University;

Zhejiang Machinery and Electrical Group

Edited by:

Editorial of Journal of Mechanical & Electrical Engineering

Chief Editor:

ZHAO Qun

Vice Chief Editor:

TANG ren-zhong,

LUO Xiang-yang

Tel:

86-571-87041360,87239525

Fax:

86-571-87239571

Add:

No.9 Gaoguannong,Daxue Road,Hangzhou,China

P.C:

310009

E-mail:

meem_contribute@163.com

Novel measuring method for over current characteristic of low voltage circuit breakers
Published:2015-04-08 author:ZHANG Hao,XIE Qiu-hui,Cai Chun-hao,FU Pei-gang,ZHAO Yong,ZHENG Lun Browse: 3534 Check PDF documents

 Novel measuring method for over current characteristic of

low voltage circuit breakers
ZHANG Hao,XIE Qiu-hui,Cai Chun-hao,FU Pei-gang,ZHAO Yong,ZHENG Lun
(Shanghai Entry-Exit Inspection and Quarantine Bureau,Shanghai 200002,China)
Abstract:Aiming at the problems of poor stability,short service life and high power consumption in the traditional equipments
measuring over- current characteristic for low voltage circuit breaker,the digital controlled power supply technology and a novel
machinery structure was investigated. Based on two technology above,a novel measuring method for over current characteristic test was
proposed. After the analysis of electrical circuit diagram,the relationship between the scheme and the mathematical model was
established and a method base on digital root mean square algorithm for current regulation was presented. The novel machinery structure
was proposed for low power consumption. The equipment designed by the proposed measuring method were evaluated on the two aspects
above:power supply technology and machinery structure. A few diagrams of experimental waveforms,a picture of the hardware circuit and
an engineering drawings of machinery structure were given. The over current inspection test of low voltage circuit breakers was tested by
the proposed equipment. The experimental results indicate that the accuracy,stability and life time of the proposed equipment are better
than the traditional ones.
Key words:delayed tripping characteristic of low voltage circuit breakers;digital controlled power supply